Tiger Tiger Tiger
GCK SERIES AC L.V. DRAWABLE

GCK series AC L.V. DRAWABLE SWITCH PANEL

General Introduction:

The device is used as low voltage complete set of power distribution device of electricity generation, power distribution of power supply system, and is used for motor centralized control, passive power compensation, with three-phase AC frequency 50 (60)Hz, rated voltage 415 V (400V, 600V), rated current 4000A or below.

Technical Specification:

 

 

Rate insulation voltage
AC600V
Rated work voltage
AC380V
Rated current of horizontal busbar
1250A,1600A,2000A,2500A, 3200A,4000A
Rated current of vertical busbar
1000A
Max. current of power-feeding circuit
2500A
Max. current of drawer loop
630A
Rated frequency
50Hz(60Hz)
Peak withstand voltage value of level busbar
132kA
Transient withstand current of level busbar(1S virtual value)
60 kA
Withstand current peak value of vertical busbar
63 kA
Transient withstand current of vertical busbar (1S virtual value)
30 kA
Rated work frequency withstand voltage
2500V
Secondary work frequency withstand voltage
2500V
Protection level of housing
IP30, IP40
Outer dimensions(W×D×H, mm)
600(800,1000)×80(1000)×2200

Standards Adopted

1, GB7251 Low -Voltage Full-Set Switch Device and Control Device

 

2, JB/T9661Low- Voltage Drawer Full-Set Switch Device

 

3, IEC60439-1Low- Voltage Full-Set Switch Device and Control Device

Parameters Required for Design

Main loop sheme and arrangement
Auxiliary loop control and wiring principles
Plane layout of switch cabinet in power distribution room
Cable entry&exit method and interface requirments
Detailed specifications and parameters of components in the cabinets
Color demands of the switch panels surface or follow our standards

GCK low voltage switch cabinet     Click To View »